SIINEOS HTTP API reference

Overview

This document describes the HTTP REST API exposed by the SMAC-Server application. The API is served on port 80 (HTTP) and port 443 (HTTPS, when a TLS certificate is configured). All endpoints are prefixed with /api/v1.

The following table lists the top-level API areas. Each area is documented in its own section below.

General endpoint summary
Area Base Path Description
Authentication /api/v1/auth, /api/v1/sessions Login, token refresh, logout, session management → :ref:`authentication`
Users /api/v1/users User account CRUD and disable → :ref:`users`
System /api/v1/system, /api/v1/storage, /api/v1/sms Device info, metrics, networking, clock, mail, SMS, config → :ref:`system`
System Update /api/v1/system/update OTA update upload and installation → :ref:`system-update`
Time-Series Database /api/v1/vmetrics VictoriaMetrics query, export, delete, reset → :ref:`timeseries`
I/O Management /api/v1/io Units, signals, ports, connections, processing chains → :ref:`io-management`
Synthetic Signals /api/v1/io/synthetic Virtual computed signals → :ref:`synthetic-signals`
Modbus Server /api/v1/io/endpoints/modbus Built-in Modbus TCP/RTU server and registers → :ref:`modbus-server`
Firewall /api/v1/firewall nftables rules and internet sharing → :ref:`firewall`
Alerting /api/v1/alerting Alert signals, destinations, and rules → :ref:`alerting`
Licensing /api/v1/licensing License import, list, and removal → :ref:`licensing`
Apps /api/v1/apps Application enable/disable and debug control → :ref:`apps`
Ping / Health /api/v1/ping Liveness check → :ref:`ping`

Authentication & Authorization

The API uses JSON Web Tokens (JWT) signed with the EdDSA algorithm. Two token types are issued:

  • Access Token – short-lived (3 minutes), used to authorize API requests.
  • Refresh Token – long-lived (30 days), used to obtain a new access token without re-authenticating.

Token Claims

The access token contains the following claims:

  • sub – the login name of the authenticated user (string)
  • iat – issued-at timestamp (ISO 8601)
  • exp – expiry timestamp (ISO 8601, 3 minutes after iat)
  • sid – session identifier (UUID without dashes)
  • roles – array of role name strings, e.g. ["SystemAdministrator"]

Available Roles

  • SystemAdministrator – full access to all endpoints
  • GlobalAppAdministrator – application-level administration
  • AppAdministrator – per-application administration
  • AppUser – standard user access

Authorization Header

Authenticated requests must carry the access token in one of the following ways (listed in order of preference by the server):

  1. Authorization: Bearer <accessToken>
  2. x-access-token: <accessToken> (custom header)
  3. ?access_token=<accessToken> (query parameter, used by :func:`hasSystemAdministratorAccessToken` for certain routes)

Most endpoints require the SystemAdministrator role. A small number of endpoints (ping, system information, system metrics, system clock read, licensing list, unit icon retrieval) are accessible without authentication.

Session Lifecycle

  1. Login – exchange credentials for an access + refresh token pair.
  2. Refresh – exchange a refresh token for a new access token.
  3. Logout – invalidate the refresh token (and thus the session).
  4. Close Session – delete a specific session by its ID (requires a valid access token belonging to that session).

Endpoints

POST /api/v1/auth/login

Authenticate with username and password.

  • Authentication: none

  • Request body (JSON, max 1000 bytes):

    • username (string, required) – login name
    • password (string, required) – plaintext password

    Example:

    {
      "username": "hubadmin",
      "password": "hubadmin"
    }
  • Responses:

    • 200 OK – body is JSON:

      {
        "accessToken": "eyJhbGciOiJFZERTQSIs...",
        "tokenType": "Bearer",
        "refreshToken": "a1b2c3d4e5f6..."
      }
    • 400 Bad Request – body too large or missing fields

    • 401 Unauthorized – invalid credentials

POST /api/v1/auth/refresh

Obtain a new access token using a refresh token.

  • Authentication: none

  • Request body (JSON, max 1000 bytes):

    • refreshToken (string, required)

    Example:

    {
      "refreshToken": "a1b2c3d4e5f6..."
    }
  • Responses:

    • 200 OK – body is JSON:

      {
        "accessToken": "eyJhbGciOiJFZERTQSIs...",
        "tokenType": "Bearer"
      }
    • 400 Bad Request – body too large or missing field

    • 401 Unauthorized – unknown or expired refresh token

    • 500 Internal Server Error – token creation failed

POST /api/v1/auth/logout

Invalidate a session by its refresh token.

  • Authentication: none
  • Request body (JSON, max 1000 bytes):
    • refreshToken (string, required)
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – body too large or missing field
    • 401 Unauthorized – unknown refresh token

DELETE /api/v1/sessions/{sessionId}

Close a specific session. The caller's access token must belong to the same session (sid claim must match sessionId).

  • Authentication: valid access token (any role), sid must match
  • Path parameter:
    • sessionId (string) – UUID of the session to close
  • Responses:
    • 200 OK – empty body
    • 401 Unauthorized – missing or invalid token
    • 403 Forbidden – token valid but sid does not match
    • 404 Not Found – session not found

Users

User management is exposed as a standard REST collection. The collection is a plain JSON array of objects (no "data" sub-key wrapper).

User Object Schema

  • uuid (string, required) – unique identifier (auto-generated on create)
  • loginName (string, required) – unique login name
  • fullName (string, required) – display name
  • password (string, required on create, optional on modify) – plaintext password; stored as SHA-256 hash server-side. Never returned in GET responses.
  • role (integer, required) – one of:
    • 0 – SystemAdministrator
    • 1 – GlobalAppAdministrator
    • 2 – AppAdministrator
    • 3 – AppUser
  • disabled (boolean, optional) – whether the account is disabled (defaults to false on create)

Endpoints

GET /api/v1/users

List all users (passwords are stripped).

  • Authentication: SystemAdministrator

  • Response ``200 OK`` – JSON array:

    [
      {
        "uuid": "907cc14b665a47f2963907f344f7bb73",
        "loginName": "hubadmin",
        "fullName": "HUB Administrator",
        "role": 0,
        "disabled": false
      }
    ]

GET /api/v1/users/{uuid}

Retrieve a single user.

  • Authentication: SystemAdministrator
  • Path parameter: uuid (string)
  • Response ``200 OK`` – single user object (no password)
  • Response ``404 Not Found`` – user not found

POST /api/v1/users

Create a new user.

  • Authentication: SystemAdministrator

  • Request body (JSON):

    {
      "loginName": "operator1",
      "fullName": "Operator One",
      "password": "s3cret!",
      "role": 3
    }
  • Responses:

    • 200 OK – body is the new user's UUID (string)
    • 400 Bad Request – invalid body
    • 409 Conflict – a user with the same loginName already exists

PUT /api/v1/users/{uuid}

Modify an existing user.

  • Authentication: SystemAdministrator

  • Path parameter: uuid (string)

  • Request body (JSON):

    {
      "loginName": "operator1",
      "fullName": "Operator One (renamed)",
      "password": "newPass123",
      "passwordConfirm": "newPass123",
      "role": 3,
      "disabled": false
    }

    Notes:

    • password is optional. If omitted or empty, the existing password hash is preserved.
    • passwordConfirm is accepted but stripped before storage.
    • If the user is not found and no password is supplied, the request fails.
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – invalid body
    • 404 Not Found – user not found

DELETE /api/v1/users/{uuid}

Delete a user. The built-in hubadmin account cannot be deleted.

  • Authentication: SystemAdministrator
  • Path parameter: uuid (string)
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – attempt to delete the protected hubadmin account
    • 404 Not Found – user not found

PUT /api/v1/users/disable/{uuid}

Enable or disable a user account.

  • Authentication: SystemAdministrator

  • Path parameter: uuid (string)

  • Request body (JSON):

    {
      "disabled": true
    }
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – invalid body
    • 404 Not Found – user not found

System

System-level endpoints cover device information, metrics, networking, storage, clock, mail, SMS, and configuration objects.

Endpoints

GET /api/v1/system/information

Retrieve basic system information.

  • Authentication: none

  • Response ``200 OK`` – JSON:

    {
      "systemClock": 1721560000,
      "uptime": 86400,
      "osVersion": "1.2.3 (Stable)",
      "osLicenseValid": 1,
      "osLicenseExpiryDate": "2027-01-01",
      "ipAddresses": [
        "192.168.1.10 (eth0)",
        "10.0.0.5 (wlan0)",
        "192.168.123.1 (usb0)"
      ]
    }

GET /api/v1/system/metrics

Retrieve real-time system metrics.

  • Authentication: none

  • Response ``200 OK`` – JSON:

    {
      "totalCpuUsage": 23.5,
      "brokenDownCpuUsage": { "user": 10.2, "system": 5.1, "idle": 84.7 },
      "systemLoad": 0.42,
      "memoryTotal": 2097152,
      "memoryAvailable": 1572864,
      "storageTotal": 16106127360,
      "storageAvailable": 12884901888,
      "storageBytesReadPerSecond": 1024,
      "storageBytesWrittenPerSecond": 2048,
      "eth0Rx": 1500000,
      "eth0Tx": 800000,
      "eth1Rx": 0,
      "eth1Tx": 0,
      "wlan0Rx": 500000,
      "wlan0Tx": 300000,
      "wwan0Rx": 0,
      "wwan0Tx": 0
    }

GET /api/v1/system/journal/recent

Retrieve the most recent system journal messages.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – plain-text, one message per line

GET /api/v1/system/processes

List running system processes.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – JSON array of process objects

GET /api/v1/system/networking/available-wireless-networks

Scan for available Wi-Fi networks.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – JSON array of network objects

GET /api/v1/system/clock

Read the current system clock (seconds since epoch).

  • Authentication: none

  • Response ``200 OK`` – JSON:

    1721560000

POST /api/v1/system/clock

Set the system clock.

  • Authentication: SystemAdministrator

  • Request body – plain-text Unix timestamp (seconds), max 128 bytes. Value must be greater than 1234567890.

    Example: 1721560000

  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – body too large or value out of range

POST /api/v1/system/hardware-clocks

Synchronise hardware clocks to the current system time.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – empty body

POST /api/v1/system/openvpn/client/config

Write an OpenVPN client configuration file and restart the service.

  • Authentication: SystemAdministrator
  • Request body – raw OpenVPN config text, max 64 KiB
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – body too large
    • 500 Internal Server Error – failed to write file

GET /api/v1/storage/usage

Retrieve storage usage details.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – JSON object with storage partition details

POST /api/v1/storage/docker/cleanup

Remove all Docker files except volumes.

  • Authentication: SystemAdministrator
  • Responses:
    • 200 OK – empty body
    • 500 Internal Server Error – cleanup failed

POST /api/v1/storage/docker/reset

Remove all Docker files including volumes.

  • Authentication: SystemAdministrator
  • Responses:
    • 200 OK – empty body
    • 500 Internal Server Error – reset failed

DELETE /api/v1/storage/docker/volumes/{name}

Remove a specific Docker volume.

  • Authentication: SystemAdministrator
  • Path parameter: name (string) – volume name
  • Responses:
    • 200 OK – body is the volume name
    • 404 Not Found – volume not found

POST /api/v1/system/device/identify

Trigger the device identification LED blink sequence (10 seconds).

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – empty body

POST /api/v1/system/reboot

Reboot the device.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – empty body

POST /api/v1/system/mail/test

Send a test e-mail using the supplied SMTP settings (does not persist them).

  • Authentication: SystemAdministrator

  • Request body (JSON):

    {
      "serverAddress": "smtp.example.com",
      "serverPort": 587,
      "encryptionMode": 2,
      "authenticationMethod": 2,
      "username": "mailer@example.com",
      "password": "secret",
      "senderName": "SIINEOS Hub",
      "senderAddress": "hub@example.com",
      "recipient": "admin@example.com",
      "subject": "Test",
      "body": "This is a test e-mail."
    }
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – e-mail could not be sent

POST /api/v1/sms

Send an SMS message via the cellular modem.

  • Authentication: SystemAdministrator

  • Request body (JSON, max 4 KiB):

    {
      "recipientNumbers": "+4915112345678,+491529876543",
      "text": "Alert: Temperature high on Unit 3"
    }
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – missing fields or body too large
    • 500 Internal Server Error – SMS send failed

System Configuration Objects

System settings are exposed as configuration objects. In the JSON payload, each property is wrapped in a "data" sub-key. For example:

{
  "hostname": { "data": "hub-gm100-abc123" },
  "deviceName": { "data": "Central Gateway" },
  "location": { "data": "Building 1, Room 234" }
}

The following configuration objects are available:

  • GET/POST /api/v1/system/config/datetime – timezone, NTP server, browser auto-sync
  • GET/POST /api/v1/system/config/eth0 – Ethernet 1 settings (mode, IP, DHCP server, etc.)
  • GET/POST /api/v1/system/config/eth1 – Ethernet 2 settings
  • GET/POST /api/v1/system/config/wlan0 – Wi-Fi settings (SSID, passphrase, channel, etc.)
  • GET/POST /api/v1/system/config/wwan0 – cellular modem settings (APN, PIN, roaming, etc.)
  • GET/POST /api/v1/system/config/device – hostname, device name, location
  • GET/POST /api/v1/system/config/communication-leds – LED target assignments (red, green)
  • GET/POST /api/v1/system/config/debugging – debug/trace logging, filter rules, process metrics
  • GET/POST /api/v1/system/config/services – SSH, VictoriaMetrics, Docker, memory monitor, MQTT broker, OpenVPN
  • GET/POST /api/v1/system/config/tls – CA certificate, device certificate, private key (base64-encoded PEM)
  • GET/POST /api/v1/system/config/smtp – SMTP server, port, encryption, authentication, sender, password

All configuration object endpoints require SystemAdministrator authentication.

Example – reading the device configuration:

GET /api/v1/system/config/device HTTP/1.1
Authorization: Bearer <accessToken>

Example response:

{
  "name": { "data": "Central Gateway" },
  "uuid": { "data": "abc123def456" },
  "state": { "data": true },
  "location": { "data": "Building 1, Room 234" }
}

Example – writing the device configuration:

POST /api/v1/system/config/device HTTP/1.1
Authorization: Bearer <accessToken>
Content-Type: application/json
{
  "name": { "data": "Central Gateway (renamed)" },
  "location": { "data": "Building 2, Room 100" }
}

System Update

The system update flow is a multi-step process: start an upload, send chunks, then poll for installation state.

Endpoints

POST /api/v1/system/update/upload/start

Begin a new update bundle upload.

  • Authentication: SystemAdministrator

  • Request body (JSON, max 1000 bytes):

    {
      "bytesToReceive": 536870912
    }
    • bytesToReceive (integer, required) – total size of the upload in bytes. Must be ≥ 1024 and ≤ 256 MiB.
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – body too large, size too small, or size limit exceeded
    • 500 Internal Server Error – failed to open output file

POST /api/v1/system/update/upload/chunk

Upload a chunk of the update bundle.

  • Authentication: SystemAdministrator
  • Request body – raw binary data, max 4 MiB per chunk
  • Responses:
    • 200 OK – body is the current byte offset (string), e.g. "1048576"
    • 400 Bad Request – chunk too large, file not open, or size limit exceeded

GET /api/v1/system/update/install/state

Poll the current installation progress.

  • Authentication: SystemAdministrator

  • Response ``200 OK`` – JSON:

    {
      "message": "Installing update bundle...",
      "progress": 45
    }

GET /api/v1/system/update/error

Retrieve error data from the last (or current) update attempt.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – plain-text error description (may be empty)

Time-Series Database (VictoriaMetrics)

Endpoints for querying, exporting, and managing time-series data stored in the local VictoriaMetrics instance.

Endpoints

GET /api/v1/vmetrics/timeseries

Retrieve the list of available time-series (metric labels) for a given time range.

  • Authentication: SystemAdministrator

  • Query parameters:

    • start (string, required) – start timestamp in milliseconds (≥ 13 digits)
    • end (string, required) – end timestamp in milliseconds (≥ 13 digits)
  • Responses:

    • 200 OK – JSON array of series descriptors:

      [
        { "name": "eth0_rx[unit=Gateway][signal=Throughput]", "hash": "a1b2c3d4e5f6" },
        { "name": "cpu_usage[unit=Gateway]", "hash": "f6e5d4c3b2a1" }
      ]
    • 202 Accepted – labels are still being fetched; retry later

    • 400 Bad Request – missing or invalid start/end

GET /api/v1/vmetrics/export/csv

Export time-series data as a CSV file (chunked/streaming response).

  • Authentication: SystemAdministrator

  • Query parameters:

    • start (string, required) – start timestamp in milliseconds
    • end (string, required) – end timestamp in milliseconds
    • step (string, optional) – step size in seconds (default 60)
    • rollup (string, optional) – comma-separated rollup functions: min, max, avg, sum, cnt
    • series (string, required) – comma-separated list of series hashes
    • decimalSeparator (string, optional) – "." (default) or ","
    • dateTimeFormat (string, optional) – timestamp (default), local, utc, localized, iso
    • dateTimeLocale (string, optional) – locale string, e.g. de_DE (default C)
  • Response:

    • 200 OK – chunked text/plain CSV with Content-Disposition: attachment; filename="SIINEOS-VictoriaMetrics-Export_<start>_<end>.csv"
    • 400 Bad Request – invalid parameters
    • 401 Unauthorized – missing/invalid token

    CSV format: semicolon-separated. First column is the timestamp (formatted according to dateTimeFormat), subsequent columns are one per requested series.

POST /api/v1/vmetrics/timeseries/delete

Delete one or more time-series from the database.

  • Authentication: SystemAdministrator

  • Request body (JSON): array of series hash strings

    ["a1b2c3d4e5f6", "f6e5d4c3b2a1"]
  • Responses:

    • 200 OK – empty body (deletion successful)
    • 400 Bad Request – empty or invalid body
    • 404 Not Found – one or more series not found
    • 500 Internal Server Error – HTTP error during deletion

POST /api/v1/vmetrics/reset

Reset (wipe) the VictoriaMetrics database.

  • Authentication: SystemAdministrator
  • Responses:
    • 200 OK – empty body
    • 500 Internal Server Error – reset failed

I/O Management

The I/O subsystem manages units (physical or virtual I/O devices), signals (measurable or controllable channels within a unit), and ports (connection points on a unit). All endpoints require SystemAdministrator authentication unless noted otherwise.

Units

GET /api/v1/io/units

List all I/O unit UUIDs.

  • Response ``200 OK`` – JSON array of UUID strings:

    ["907cc14b665a47f2963907f344f7bb73", "a1b2c3d4e5f60718293a4b5c6d7e8f90"]

GET /api/v1/io/units/{unitUuid}

Retrieve the announcement data for a single unit.

  • Path parameter: unitUuid (string)

  • Response ``200 OK`` – JSON:

    {
      "providerName": "Synthetic Signals",
      "providerId": "synthetic_signals",
      "providerType": 4,
      "providerConnectivity": 0,
      "uuid": "907cc14b665a47f2963907f344f7bb73",
      "address": "",
      "name": "Synthetic signals",
      "location": "",
      "enabled": true,
      "connected": true,
      "error": "",
      "icon": "icon.svg",
      "busy": false,
      "signalsBrowsable": false,
      "signalsResettable": false,
      "signalAddressesContainPinAssignment": false,
      "signals": ["sig-uuid-1", "sig-uuid-2"],
      "upstreamUnit": "",
      "upstreamPort": "",
      "ports": []
    }
  • Response ``404 Not Found`` – unit not found

POST /api/v1/io/units

Create a new I/O unit instance for the given provider.

  • Request body – plain-text provider identifier (e.g. "modbus_client")
  • Responses:
    • 200 OK – body is the new unit's UUID
    • 400 Bad Request – provider not found

DELETE /api/v1/io/units/{unitUuid}

Remove a unit and its configuration.

  • Responses:
    • 200 OK – empty body
    • 404 Not Found – unit not found

Unit Configuration

Unit settings are stored as a configuration object with the "data" sub-key pattern.

GET /api/v1/io/units/{unitUuid}/config

Read the full unit configuration.

  • Response ``200 OK`` – JSON with "data" sub-keys:

    {
      "general": {
        "name": { "data": "My Modbus Unit" },
        "uuid": { "data": "a1b2c3d4..." },
        "state": { "data": true },
        "providerId": { "data": "modbus_client" },
        "upstreamUnit": { "data": "" },
        "upstreamPort": { "data": "" },
        "signals": { "data": [ ... ] }
      },
      "data": {
        "customIcon": { "data": "" }
      }
    }

PUT /api/v1/io/units/{unitUuid}/config

Replace the full unit configuration.

  • Request body (JSON, max 4 MiB) – same structure as the GET response. The providerId must match the unit's actual provider; the uuid is overwritten with the path parameter.
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – invalid JSON or body too large
    • 404 Not Found – unit not found
    • 409 Conflict – provider ID mismatch

GET /api/v1/io/units/{unitUuid}/config/{configObjectId}

Read a specific configuration sub-object (e.g. "general", "data", or a signal's "signal" object).

  • Path parameters: unitUuid, configObjectId
  • Response ``200 OK`` – JSON with "data" sub-keys for that sub-object
  • Response ``404 Not Found`` – unit or config object not found

PUT /api/v1/io/units/{unitUuid}/config/{configObjectId}

Write a specific configuration sub-object.

  • Request body (JSON, max 4 MiB)
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – invalid JSON
    • 404 Not Found – unit or config object not found

Unit Name, Icon, and Upstream

PUT /api/v1/io/units/{unitUuid}/name

Rename a unit.

  • Request body – plain-text name, max 256 bytes
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – body too large
    • 404 Not Found – unit not found

GET /api/v1/io/units/{unitUuid}/icon

Retrieve the unit's custom icon (binary).

  • Authentication: none
  • Query parameter: <hash> (string) – hash of the icon data (for cache-busting)
  • Response ``200 OK`` – binary image data
  • Response ``404 Not Found`` – unit not found

PUT /api/v1/io/units/{unitUuid}/icon

Upload a custom icon for the unit.

  • Request body – binary image data, max 128 KiB
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – body too large
    • 404 Not Found – unit not found

DELETE /api/v1/io/units/{unitUuid}/icon

Remove the custom icon (reverts to the provider default).

  • Responses:
    • 200 OK – empty body
    • 404 Not Found – unit not found

PUT /api/v1/io/units/{unitUuid}/upstream

Set the upstream unit and port for daisy-chained units.

  • Request body (JSON, max 256 bytes):

    {
      "unit": "upstream-unit-uuid",
      "port": "port-uuid"
    }
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – body too large or invalid JSON
    • 404 Not Found – unit not found

Unit Control

POST /api/v1/io/units/{unitUuid}/control/{action}

Send a provider-specific control command to a unit.

  • Path parameters: unitUuid, action (provider-defined string)
  • Request body – provider-specific payload, max 4 MiB
  • Responses:
    • 200 OK – provider-specific response
    • 400 Bad Request – body too large
    • 404 Not Found – unit not found
    • 501 Not Implemented – unit does not support control

Ports

GET /api/v1/io/units/{unitUuid}/ports/{portUuid}/config

Read a port's configuration.

  • Response ``200 OK`` – JSON with "data" sub-keys
  • Response ``404 Not Found`` – unit or port not found

POST /api/v1/io/units/{unitUuid}/ports/{portUuid}/config

Write a port's configuration.

  • Request body (JSON) – same structure as GET response
  • Responses:
    • 200 OK – empty body
    • 404 Not Found – unit or port not found

Signals

GET /api/v1/io/units/{unitUuid}/signals

List signal UUIDs for a unit.

  • Response ``200 OK`` – JSON array of UUID strings

GET /api/v1/io/units/{unitUuid}/signals/{signalUuid}

Retrieve a single signal's announcement data.

  • Response ``200 OK`` – JSON:

    {
      "uuid": "sig-uuid-1",
      "type": "Temperature",
      "identifier": "temp_1",
      "address": "0",
      "name": "Temperature Sensor 1",
      "group": "Sensors",
      "dataSeriesSet": "",
      "readable": true,
      "writable": false,
      "enabled": true,
      "dataType": 6,
      "unit": "°C",
      "decimals": 1,
      "minValue": -40,
      "maxValue": 125,
      "color": "#00dbc9",
      "visualization": "gauge"
    }

POST /api/v1/io/units/{unitUuid}/signals

Add a single new signal to a unit.

  • Response ``200 OK`` – body is the new signal's UUID
  • Response ``404 Not Found`` – unit not found

PUT /api/v1/io/units/{unitUuid}/signals

Add multiple signals to a unit in one request.

  • Request body (JSON): array of signal property objects

    [
      { "name": { "data": "Signal A" }, "address": { "data": "0" } },
      { "name": { "data": "Signal B" }, "address": { "data": "1" } }
    ]
  • Response ``200 OK`` – JSON array of new signal UUIDs

  • Response ``400 Bad Request`` – invalid JSON

  • Response ``404 Not Found`` – unit not found

DELETE /api/v1/io/units/{unitUuid}/signals

Remove multiple signals from a unit.

  • Query parameter: uuids (string, required) – comma-separated signal UUIDs

    Example: ?uuids=sig-1,sig-2,sig-3

  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – missing uuids parameter
    • 404 Not Found – unit not found
    • 500 Internal Server Error – removal failed

POST /api/v1/io/units/{unitUuid}/signals/{signalUuid}/duplicate

Duplicate an existing signal with a new name.

  • Request body (JSON):

    {
      "name": "Temperature Sensor 1 (copy)"
    }
  • Responses:

    • 200 OK – body is the new signal's UUID
    • 400 Bad Request – missing name field
    • 404 Not Found – unit or source signal not found
    • 500 Internal Server Error – duplication failed

Signal Configuration

Signal settings use the configuration object pattern with "data" sub-keys. See :ref:`signal-processing-chains` for the full key reference.

GET /api/v1/io/units/{unitUuid}/signals/{signalUuid}/config

Read a signal's configuration.

  • Response ``200 OK`` – JSON with "data" sub-keys (see :ref:`signal-processing-chains`)

PUT /api/v1/io/units/{unitUuid}/signals/{signalUuid}/config

Write a signal's configuration.

  • Request body (JSON) – same structure as GET response
  • Responses:
    • 200 OK – empty body
    • 404 Not Found – unit or signal not found

PUT /api/v1/io/units/{unitUuid}/signals/config

Write configuration for multiple signals in one request.

  • Query parameter: uuids (string, required) – comma-separated signal UUIDs
  • Request body (JSON) – configuration object (applied to all listed signals)
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – invalid JSON
    • 404 Not Found – unit or any signal not found

PUT /api/v1/io/units/{unitUuid}/signals/clear

Remove all signals from a unit.

  • Responses:
    • 200 OK – empty body
    • 404 Not Found – unit not found
    • 500 Internal Server Error – clear failed

PUT /api/v1/io/units/{unitUuid}/signals/reset

Reset specific signals (e.g. zero counters).

  • Request body (JSON): array of signal UUIDs

    ["sig-uuid-1", "sig-uuid-2"]
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – invalid JSON
    • 404 Not Found – unit not found

POST /api/v1/io/units/{unitUuid}/signals/{signalUuid}/control/{action}

Send a signal-specific control command.

  • Path parameters: unitUuid, signalUuid, action
  • Request body – provider-specific payload, max 4 MiB
  • Responses:
    • 200 OK – provider-specific response
    • 400 Bad Request – missing action or body too large
    • 404 Not Found – unit or signal not found
    • 501 Not Implemented – signal does not support control

I/O Connections

I/O connections define signal processing chains that route a source signal's output to a destination signal's input. The collection is a plain JSON array (no "data" wrapper).

Connection Object Schema

  • uuid (string, required) – unique identifier
  • source (object, required):
    • unit (string) – source unit UUID
    • signal (string) – source signal UUID
  • destination (object, required):
    • unit (string) – destination unit UUID
    • signal (string) – destination signal UUID
  • signalProcessings (array, optional) – array of processing chain configuration objects (see :ref:`signal-processing-chains`)
  • disabled (boolean, optional) – whether the connection is disabled

Endpoints:

  • GET /api/v1/io/connections – list all connections
  • GET /api/v1/io/connections/{uuid} – get one connection
  • POST /api/v1/io/connections – create a connection
  • PUT /api/v1/io/connections/{uuid} – modify a connection
  • DELETE /api/v1/io/connections/{uuid} – delete a connection
  • PUT /api/v1/io/connections/disable/{uuid} – enable/disable a connection

All require SystemAdministrator authentication.

Default Signal Processing Chain Configuration

GET /api/v1/io/signal-processing/config/default

Read the default (template) signal processing chain configuration. This is a read-only configuration object.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – JSON with "data" sub-keys (see :ref:`signal-processing-chains`)

Signal Processing Chains

Every I/O signal has an embedded signal processing chain that transforms the raw measurement value through a sequence of optional stages before producing the final output. The chain is configured via the signal's configuration object and uses the "data" sub-key pattern.

Chain Stage Order

The processing stages are applied in the following fixed order:

  1. Pre-processing (mathematical expression)
  2. Linear scaling
  3. Delta
  4. Limit
  5. Threshold comparison
  6. Comparator
  7. Edge detection
  8. Time derivative
  9. Aggregation
  10. Post-processing (mathematical expression)

Configuration Keys Reference

All keys below appear in the signal's configuration JSON. Each value is wrapped in { "data": <value> }.

Pre-processing

  • preProcessingEnabled (boolean) – enable/disable the stage
  • preProcessingExpression (string) – mathematical expression using variable x for the input value. Example: "1.25 + (x / 2)"

Linear Scaling

  • linearScalingEnabled (boolean)
  • linearScalingX1 (float) – minimum input value
  • linearScalingY1 (float) – corresponding minimum output value
  • linearScalingX2 (float) – maximum input value
  • linearScalingY2 (float) – corresponding maximum output value

Delta

  • deltaEnabled (boolean)
  • deltaMode (unsigned integer):
    • 0 – absolute difference to previous value
    • 1 – relative change from previous value
    • 2 – relative change in percent
    • 3 – sign difference from previous value

Limit

  • limitEnabled (boolean)
  • limitDownwards (boolean) – apply lower limit
  • limitMinimumValue (float) – lower bound
  • limitUpwards (boolean) – apply upper limit
  • limitMaximumValue (float) – upper bound

Threshold Comparison

  • thresholdComparisonEnabled (boolean)
  • thresholdComparisonMode (unsigned integer):
    • 0 – signal is above threshold
    • 1 – signal is above or equal
    • 2 – signal is below threshold
    • 3 – signal is below or equal
  • thresholdComparisonValue (unsigned integer) – threshold value

Comparator

  • comparatorEnabled (boolean)
  • comparatorLowerThreshold (float)
  • comparatorUpperThreshold (float)
  • comparatorOutputValueOff (float) – output when below lower threshold
  • comparatorOutputValueOn (float) – output when above upper threshold
  • comparatorTimerIntervalOff (unsigned integer, ms) – required duration below lower threshold
  • comparatorTimerIntervalOn (unsigned integer, ms) – required duration above upper threshold

Edge Detection

  • edgeDetectionEnabled (boolean)
  • edgeDetectionCountRising (boolean) – count rising edges
  • edgeDetectionCountFalling (boolean) – count falling edges

Time Derivative

  • timeDerivativeEnabled (boolean)
  • timeDerivativeTimeBase (unsigned integer):
    • 0 – per second (Δx/s)
    • 1 – per minute (Δx/min)
    • 2 – per hour (Δx/h)
    • 3 – per day (Δx/d)

Aggregation

  • aggregationEnabled (boolean)
  • aggregationType (unsigned integer):
    • 0 – minimum value
    • 1 – maximum value
    • 2 – average value
    • 3 – oldest value
    • 4 – sum of all values
    • 5 – median
  • aggregationInterval (unsigned integer, seconds) – window size
  • aggregationUpdateMode (unsigned integer):
    • 0 – continuously (update on every sample)
    • 1 – periodically (update at end of interval)

Post-processing

  • postProcessingEnabled (boolean)
  • postProcessingExpression (string) – mathematical expression using variable x. Example: "x * 1.05"

Signal Metadata Keys

In addition to the processing chain keys, the signal configuration includes:

  • name (string) – display name
  • uuid (string, read-only) – signal UUID
  • enabled (boolean) – enable/disable the signal
  • vmetricsPushEnabled (boolean) – record values to VictoriaMetrics
  • vmetricsPushInterval (unsigned integer, seconds) – recording interval
  • useCustomIdentifier (boolean)
  • customIdentifier (string) – custom identifier (overrides auto-generated)
  • group (string) – grouping label
  • dataSeriesSet (string) – data series set label
  • siPrefix (unsigned integer) – SI prefix (0 = none, 3 = k, 9 = µ, etc.)
  • measurementUnit (string) – unit string (e.g. "DegreeCelsius")
  • decimals (unsigned integer) – number of decimal places (0–5)
  • customDataType (unsigned integer) – override data type (0 = keep original)
  • visualizationType (string) – "none", "gauge", "led", "counter"
  • color (string) – hex colour or named colour
  • minimumValue (double) – display minimum
  • maximumValue (double) – display maximum

Example – Full Signal Configuration

{
  "name": { "data": "Motor Temperature" },
  "uuid": { "data": "a1b2c3d4e5f6" },
  "enabled": { "data": true },
  "vmetricsPushEnabled": { "data": true },
  "vmetricsPushInterval": { "data": 60 },
  "useCustomIdentifier": { "data": false },
  "customIdentifier": { "data": "" },
  "group": { "data": "Motor" },
  "dataSeriesSet": { "data": "" },
  "siPrefix": { "data": 0 },
  "measurementUnit": { "data": "DegreeCelsius" },
  "decimals": { "data": 1 },
  "customDataType": { "data": 0 },
  "visualizationType": { "data": "gauge" },
  "color": { "data": "#00dbc9" },
  "minimumValue": { "data": -40 },
  "maximumValue": { "data": 150 },
  "preProcessingEnabled": { "data": false },
  "preProcessingExpression": { "data": "x" },
  "linearScalingEnabled": { "data": true },
  "linearScalingX1": { "data": 0 },
  "linearScalingY1": { "data": -40 },
  "linearScalingX2": { "data": 255 },
  "linearScalingY2": { "data": 150 },
  "deltaEnabled": { "data": false },
  "deltaMode": { "data": 0 },
  "limitEnabled": { "data": true },
  "limitDownwards": { "data": true },
  "limitMinimumValue": { "data": -40 },
  "limitUpwards": { "data": true },
  "limitMaximumValue": { "data": 150 },
  "thresholdComparisonEnabled": { "data": false },
  "thresholdComparisonMode": { "data": 0 },
  "thresholdComparisonValue": { "data": 0 },
  "comparatorEnabled": { "data": false },
  "comparatorLowerThreshold": { "data": 0 },
  "comparatorUpperThreshold": { "data": 0 },
  "comparatorOutputValueOff": { "data": 0 },
  "comparatorOutputValueOn": { "data": 1 },
  "comparatorTimerIntervalOff": { "data": 0 },
  "comparatorTimerIntervalOn": { "data": 0 },
  "edgeDetectionEnabled": { "data": false },
  "edgeDetectionCountRising": { "data": false },
  "edgeDetectionCountFalling": { "data": false },
  "timeDerivativeEnabled": { "data": false },
  "timeDerivativeTimeBase": { "data": 0 },
  "aggregationEnabled": { "data": false },
  "aggregationType": { "data": 2 },
  "aggregationInterval": { "data": 60 },
  "aggregationUpdateMode": { "data": 0 },
  "postProcessingEnabled": { "data": false },
  "postProcessingExpression": { "data": "x" }
}

Synthetic Signals

Synthetic signals are virtual I/O signals computed from other signals using arithmetic or logical expressions. The collection is a plain JSON array.

Synthetic Signal Object Schema

  • uuid (string, required) – unique identifier
  • name (string, required) – display name
  • enabled (boolean, optional) – defaults to true
  • source1 (object, required):
    • unit (string) – source unit UUID
    • signal (string) – source signal UUID
  • source2 (object, required):
    • unit (string) – second source unit UUID
    • signal (string) – second source signal UUID
  • calculation (string, required) – the calculation expression. Supported values:
    • "+", "-", "*", "/" – arithmetic on A and B
    • "&&", "||" – logical AND / OR
    • ".." – latch (A sets to 1, B resets to 0)
    • "+." – counter with reset (A = count, B = reset trigger)
    • "++" – counter without reset (A = count)
    • Any other string – evaluated as a mathematical expression with variables A, B, P (previous value) and access to Math.* functions

Endpoints

GET /api/v1/io/synthetic/signals

List all synthetic signals.

  • Authentication: SystemAdministrator
  • Response ``200 OK`` – JSON array

GET /api/v1/io/synthetic/signals/{uuid}

Get a single synthetic signal.

  • Response ``200 OK`` – single object
  • Response ``404 Not Found`` – not found

POST /api/v1/io/synthetic/signals

Create a synthetic signal.

  • Request body (JSON):

    {
      "name": "Flow Difference",
      "source1": { "unit": "unit-uuid-1", "signal": "sig-uuid-1" },
      "source2": { "unit": "unit-uuid-2", "signal": "sig-uuid-2" },
      "calculation": "-"
    }
  • Responses:

    • 200 OK – body is the new UUID
    • 400 Bad Request – invalid body

PUT /api/v1/io/synthetic/signals/{uuid}

Modify a synthetic signal.

  • Request body (JSON) – same schema as create
  • Responses:
    • 200 OK – empty body
    • 404 Not Found – not found

PUT /api/v1/io/synthetic/signals

Replace all synthetic signals at once.

  • Request body (JSON) – array of synthetic signal objects
  • Responses:
    • 200 OK – empty body
    • 400 Bad Request – invalid body

DELETE /api/v1/io/synthetic/signals/{uuid}

Delete a synthetic signal.

  • Responses:
    • 200 OK – empty body
    • 404 Not Found – not found

PUT /api/v1/io/synthetic/signals/disable/{uuid}

Enable/disable a synthetic signal.

  • Request body: { "disabled": true }

POST /api/v1/io/synthetic/signals/{sourceUuid}/clone/{destUuid}

Clone the calculation settings from one synthetic signal to another.

  • Path parameters: sourceUuid, destUuid
  • Responses:
    • 200 OK – empty body
    • 404 Not Found – either signal not found

POST /api/v1/io/synthetic/signals/{uuid}/name/propagate

Propagate the name from the registry entry to the live I/O signal.

  • Responses:
    • 200 OK – empty body
    • 404 Not Found – signal not found

POST /api/v1/io/synthetic/signals/{uuid}/name/update

Update the registry name to match the live I/O signal name.

  • Responses:
    • 200 OK – empty body
    • 404 Not Found – signal not found
    • 500 Internal Server Error – registry update failed

Modbus Server Endpoint

The built-in Modbus server exposes TCP and RTU interfaces with configurable registers.

Endpoints

GET/POST /api/v1/io/endpoints/modbus/tcp

Read/write Modbus TCP server settings.

  • Authentication: SystemAdministrator
  • Configuration keys ("data" sub-key pattern):
    • enabled (boolean) – enable/disable the TCP server
    • networkAddress (string) – listen address (default "0.0.0.0")
    • networkPort (unsigned integer) – listen port (default 502)

GET/POST /api/v1/io/endpoints/modbus/rtu

Read/write Modbus RTU slave settings.

  • Authentication: SystemAdministrator
  • Configuration keys:
    • enabled (boolean)
    • rtuBusInterface (unsigned integer):
      • 0 – serial port
      • 1 – builtin RS485 interface
      • 2 – backplane bus
    • rtuSerialPortName (string) – e.g. "ttyUSB0"
    • rtuBaudRate (unsigned integer) – e.g. 115200
    • rtuDataBits (unsigned integer) – 5, 6, 7, or 8
    • rtuParity (unsigned integer):
      • 0 – no parity
      • 2 – even
      • 3 – odd
      • 4 – space
      • 5 – mark
    • rtuStopBits (unsigned integer):
      • 1 – 1 stop bit
      • 2 – 2 stop bits
      • 3 – 1.5 stop bits
    • modbusId (unsigned integer) – Modbus slave address (1–254)

GET/POST/PUT/DELETE /api/v1/io/endpoints/modbus/registers

Manage Modbus register mappings. The collection is a plain JSON array.

Register Object Schema

  • uuid (string, required) – unique identifier
  • type (integer) – Modbus register type
  • address (integer) – register address
  • dataType (integer, optional) – data type:
    • 0 – unsigned small integer (1 register)
    • 1 – signed small integer (1 register)
    • 2 – unsigned integer (2 registers)
    • 3 – signed integer (2 registers)
    • 4 – float (2 registers)
    • 5 – unsigned big integer (4 registers)
    • 6 – signed big integer (4 registers)
    • 7 – double (4 registers)
  • ioMode (integer) – 0 = read from signal, 1 = write to signal
  • signal (object):
    • unit (string) – target unit UUID
    • signal (string) – target signal UUID

Example register:

{
  "uuid": "reg-uuid-1",
  "type": 3,
  "address": 0,
  "dataType": 4,
  "ioMode": 0,
  "signal": { "unit": "unit-uuid-1", "signal": "sig-uuid-1" }
}

Firewall

Firewall rules are managed as four separate collections (all plain JSON arrays with move-up/move-down support) plus internet connection sharing settings.

Rule Object Schema (common fields)

  • uuid (string, required)
  • enabled (boolean, optional, default true)
  • networkProtocol (string) – protocol identifier
  • inputInterface / outputInterface (string) – interface name
  • sourceAddress / destinationAddress (string) – IP or CIDR
  • destinationPorts (string) – space-separated port list
  • action (string) – rule action (accept/drop)

Endpoints

Incoming Rules

  • GET /api/v1/firewall/rules/incoming – list
  • GET /api/v1/firewall/rules/incoming/{uuid} – get one
  • POST /api/v1/firewall/rules/incoming – create
  • PUT /api/v1/firewall/rules/incoming/{uuid} – modify
  • DELETE /api/v1/firewall/rules/incoming/{uuid} – delete
  • PUT /api/v1/firewall/rules/incoming/{uuid}/up – move up
  • PUT /api/v1/firewall/rules/incoming/{uuid}/down – move down

Outgoing Rules

  • GET /api/v1/firewall/rules/outgoing – list
  • GET /api/v1/firewall/rules/outgoing/{uuid} – get one
  • POST /api/v1/firewall/rules/outgoing – create
  • PUT /api/v1/firewall/rules/outgoing/{uuid} – modify
  • DELETE /api/v1/firewall/rules/outgoing/{uuid} – delete
  • PUT /api/v1/firewall/rules/outgoing/{uuid}/up – move up
  • PUT /api/v1/firewall/rules/outgoing/{uuid}/down – move down

IP Forwarding Rules

  • GET /api/v1/firewall/rules/ipforwarding – list
  • GET /api/v1/firewall/rules/ipforwarding/{uuid} – get one
  • POST /api/v1/firewall/rules/ipforwarding – create
  • PUT /api/v1/firewall/rules/ipforwarding/{uuid} – modify
  • DELETE /api/v1/firewall/rules/ipforwarding/{uuid} – delete
  • PUT /api/v1/firewall/rules/ipforwarding/{uuid}/up – move up
  • PUT /api/v1/firewall/rules/ipforwarding/{uuid}/down – move down

Additional fields for IP forwarding rules:

  • inputInterface (string)
  • outputInterface (string)
  • sourceAddress (string)
  • destinationAddress (string)

Port Forwarding Rules

  • GET /api/v1/firewall/rules/portforwarding – list
  • GET /api/v1/firewall/rules/portforwarding/{uuid} – get one
  • POST /api/v1/firewall/rules/portforwarding – create
  • PUT /api/v1/firewall/rules/portforwarding/{uuid} – modify
  • DELETE /api/v1/firewall/rules/portforwarding/{uuid} – delete
  • PUT /api/v1/firewall/rules/portforwarding/{uuid}/up – move up
  • PUT /api/v1/firewall/rules/portforwarding/{uuid}/down – move down

Additional fields for port forwarding rules:

  • localPort (string) – local port to forward to
  • destinationPort (string) – destination port
  • destinationAddress (string) – target IP
  • masquerade (boolean, optional) – enable masquerade

Internet Connection Sharing

GET /api/v1/firewall/internet/sharing

Read internet connection sharing settings.

  • Authentication: SystemAdministrator

  • Response ``200 OK`` – JSON:

    {
      "enabled": true,
      "inputInterfaces": ["eth0", "wlan0"],
      "outputInterface": "wwan0"
    }

POST /api/v1/firewall/internet/sharing

Write internet connection sharing settings.

  • Authentication: SystemAdministrator

  • Request body (JSON, max 100000 bytes):

    {
      "enabled": true,
      "inputInterfaces": ["eth0", "wlan0"],
      "outputInterface": "wwan0"
    }
    • enabled (boolean, required)
    • inputInterfaces (array of strings, required) – interfaces to share from
    • outputInterface (string, required) – interface to share through. Must be one of: eth0, eth1, wlan0, wwan0, tun0, docker0
  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – invalid body or unknown interface

Alerting

The alerting subsystem comprises three collections: signals (conditions to monitor), destinations (notification targets), and rules (bindings between signals and destinations). All are plain JSON arrays with disable support.

Alert Signal Object Schema

  • uuid (string, required)
  • name (string, required)
  • disabled (boolean, optional)
  • evalMode (string, required) – one of:
    • "binary"
    • "thresholds"
    • "counter"
    • "cycles"
  • evalParams (object, required):
    • For binary: lowActive (boolean)
    • For thresholds: comparison (string: "above", "aboveOrEqual", "below", "belowOrEqual", "equal", "insideRange", "outsideRange"), lowerThreshold (number), upperThreshold (number, for range comparisons)
    • For counter: counterStepSize (number)
    • For cycles: pulseThreshold (number)
  • source (object, required):
    • unit (string) – source I/O unit UUID
    • signal (string) – source I/O signal UUID
  • cycleTime (number, optional) – timeout in seconds for counter/cycles modes
  • stateTransition (object, optional):
    • alarmDelayEnabled (boolean)
    • alarmDelay (number, seconds)
    • okDelayEnabled (boolean)
    • okDelay (number, seconds)
  • severity (string, optional) – "none", "low", "medium", "high"
  • category (string, optional) – free-text category label

Alert Destination Object Schema

  • uuid (string, required)

  • name (string, required)

  • disabled (boolean, optional)

  • type (string, required) – one of: "email", "sms", "webhook", "app", "iosignal", "mqtt", "vmetrics"

  • Type-specific sub-objects:

    • email: recipients (string, comma-separated), subject (string), body (string)
    • sms: recipients (string), text (string)
    • webhook: url (string), body (string), method (string: "GET", "POST", "PUT", "DELETE")
    • app: appId (string)
    • iosignal: unit (string), signal (string)
    • mqtt: brokerAddress (string), brokerPort (integer), topic (string), data (string)
    • vmetrics: metricName (string)

    Placeholder tokens available in text fields: {{NAME}}, {{STATE}}, {{VALUE}}, {{SEVERITY}}, {{CATEGORY}}, {{CLASSIFICATION}}, {{ID}}, {{SOURCENAME}}, {{SOURCEVALUE}}, {{SOURCELOCATION}}, {{HOSTNAME}}, {{DEVICENAME}}, {{DEVICELOCATION}}

Alert Rule Object Schema

  • uuid (string, required)
  • name (string, required)
  • disabled (boolean, optional)
  • alertSignals (array, required) – array of { "uuid": "<signal-uuid>" } objects, or [{ "uuid": "*" }] to match all signals
  • destinations (array, required) – array of { "uuid": "<destination-uuid>" } objects
  • triggers (object, required):
    • ok (boolean) – trigger on OK state
    • alarm (boolean) – trigger on alarm state
  • severityLevels (object, required):
    • all (boolean) – match all severities
    • none (boolean) – include "no severity"
    • low (boolean)
    • medium (boolean)
    • high (boolean)
  • repetition (integer, optional) – re-notification interval in minutes (0 or omitted = no repetition)

Endpoints

Alert Signals

  • GET /api/v1/alerting/signals – list
  • GET /api/v1/alerting/signals/{uuid} – get one
  • POST /api/v1/alerting/signals – create
  • PUT /api/v1/alerting/signals/{uuid} – modify
  • DELETE /api/v1/alerting/signals/{uuid} – delete
  • PUT /api/v1/alerting/signals/disable/{uuid} – enable/disable

Alert Destinations

  • GET /api/v1/alerting/destinations – list
  • GET /api/v1/alerting/destinations/{uuid} – get one
  • POST /api/v1/alerting/destinations – create
  • PUT /api/v1/alerting/destinations/{uuid} – modify
  • DELETE /api/v1/alerting/destinations/{uuid} – delete
  • PUT /api/v1/alerting/destinations/disable/{uuid} – enable/disable

Alert Rules

  • GET /api/v1/alerting/rules – list
  • GET /api/v1/alerting/rules/{uuid} – get one
  • POST /api/v1/alerting/rules – create
  • PUT /api/v1/alerting/rules/{uuid} – modify
  • DELETE /api/v1/alerting/rules/{uuid} – delete
  • PUT /api/v1/alerting/rules/disable/{uuid} – enable/disable

All alerting endpoints require SystemAdministrator authentication.

Licensing

License management for the SIINEOS platform and third-party applications.

Endpoints

GET /api/v1/licensing/licenses

List all installed licenses.

  • Authentication: none

  • Response ``200 OK`` – JSON array:

    [
      {
        "id": "lic-uuid-1",
        "productId": "de.inhub.siineos",
        "productName": "SIINEOS Hub",
        "productVersion": "1.2.3",
        "productSize": 512,
        "valid": true,
        "validFrom": "2024-01-01",
        "validUntil": "2027-01-01",
        "licensee": "ACME Corp"
      }
    ]

POST /api/v1/licensing/licenses

Import a license by uploading a license certificate file.

  • Authentication: SystemAdministrator

  • Request body – raw binary license certificate file (max 100000 bytes). The server parses the certificate and extracts license metadata internally. No JSON is sent by the client.

  • Responses:

    • 200 OK – body is JSON with the imported license metadata:

      {
        "id": "lic-uuid-1",
        "productId": "de.inhub.siineos",
        "productName": "SIINEOS Hub",
        "productVersion": "1.2.3",
        "productSize": 512,
        "valid": true,
        "validFrom": "2024-01-01",
        "validUntil": "2027-01-01",
        "licensee": "ACME Corp"
      }
    • 400 Bad Request – body too large

    • 409 Conflict – a license with the same ID is already installed

    • 415 Unsupported Media Type – the certificate is not valid

    • 422 Unprocessable Entity – the certificate is valid but the license is not accepted (e.g. expired)

DELETE /api/v1/licensing/licenses/{licenseId}

Remove a license.

  • Authentication: SystemAdministrator
  • Path parameter: licenseId (string)
  • Responses:
    • 200 OK – empty body
    • 404 Not Found – license not found
    • 500 Internal Server Error – removal failed

Apps

Application control endpoints for managing installed apps on the hub.

Endpoints

PUT /api/v1/apps/{appId}/control/{controlProperty}

Set a control property on an app.

  • Authentication: SystemAdministrator

  • Path parameters:

    • appId (string) – application identifier
    • controlProperty (string) – one of: "enabled", "debug", "trace"
  • Request body – JSON boolean (max 10 bytes)

    Example: true

  • Responses:

    • 200 OK – empty body
    • 400 Bad Request – body too large or invalid JSON
    • 404 Not Found – unknown control property

Ping / Health

GET /api/v1/ping

Health-check endpoint.

  • Authentication: none
  • Response ``200 OK`` – empty body

Error Handling

The API uses standard HTTP status codes. Error responses generally have an empty body or a short plain-text message.

Status Code Reference

  • 400 Bad Request – malformed request body, missing required fields, body exceeds size limit, invalid parameter values, or a business-rule violation (e.g. deleting the protected admin account).

    Typical body: empty string or a short message such as "upload file size too small" or "body length limit exceeded".

  • 401 Unauthorized – missing, malformed, or expired access token; or invalid credentials during login.

    Typical body: "Authentication required" or empty.

  • 403 Forbidden – valid token but insufficient role (e.g. a non-admin user accessing an admin-only endpoint), or session ID mismatch.

    Typical body: "Admin privileges required" or "Invalid access token".

  • 404 Not Found – the requested resource (user, unit, signal, license, session, etc.) does not exist.

    Typical body: empty string.

  • 409 Conflict – a resource with the same unique key already exists (e.g. duplicate user login name, duplicate license ID, provider ID mismatch on unit config write).

    Typical body: empty string or the conflicting value.

  • 415 Unsupported Media Type – the uploaded file is not a valid license certificate.

  • 422 Unprocessable Entity – the request is syntactically correct but semantically invalid (e.g. license certificate is well-formed but the license is expired or not accepted).

  • 500 Internal Server Error – an unexpected server-side failure (e.g. file I/O error, external service failure, database write failure).

    Typical body: empty string.

  • 501 Not Implemented – the requested operation is not supported by the target unit or signal.

    Typical body: "Not implemented".

General Notes

  • All JSON request bodies have a maximum size of 1 MiB unless otherwise stated (e.g. 4 MiB for unit config writes, 128 KiB for icon uploads, 256 MiB for update bundle chunks).
  • UUIDs in the API are 32-character hexadecimal strings without dashes.
  • Timestamps in query parameters for the time-series API are in milliseconds since epoch (13 digits).
  • The "data" sub-key pattern applies exclusively to configuration-object endpoints. Collection endpoints (users, firewall rules, alerting, I/O connections, synthetic signals, Modbus registers) use plain JSON objects without the wrapper.